SA

Saddle with spigot, SDR 11

Saddle with spigot SA SDR 11

  • Gas, water and H2
  • Working pressure: MOP (gas) 10 bar, PFA (water) 16 bar
  • Material: PE 100
  • Saddle component with clamp
  • Tapping under pressure possible
  • Safety technology
  • DVGW test mark: DV-8601AU2248 and DV-8606AU2249.

Note:

For the pressure-free tapping, there is our drilling device FWAB.

For tapping under pressure, we recommend the drilling tool from Hütz & Baumgarten (www.huetz-baumgarten.de).

If required, please contact our hotline: +49 621 486-2325.

Go back Data sheet

Areas of Application

The FRIALEN-Spigot Saddles SA are used for tapping of depressurised gas- and waterpipes as well as for pressure drainage. The branch line is connected with the outlet spigot by using a FRIALEN coupler UB.

Assembly Instructions

The fusion of the HD-PE distribution pipes and the house connections with FRIALEN-Spigot Saddles SA takes place by FRIALEN-fusing –leakproof and longitudinally strong.

The saddle and the outlet spigot have to be prepared according to the general installation instructions (see “Assembly Instructions” for “FRIALEN-Safety Fittings for house connections and distribution pipes up to d 225”). This involves removing the oxide skin and cleaning the pipes covered by the saddle and the coupler.

Swarfless tapping up to Ø 46 mm, from Ø 65 to Ø 123 mm extremely swarfreduced by using the tapping equipment of Hütz + Baumgarten.

For pipes without pressure spigot saddles SA can be used as a T-piece with a reduced outlet.

For tapping the main line under operating pressure, please contact our Application Engineering Department.

Good reasons for using the FRIALEN-SA:

  • Compact construction

  • exposed heating element for optimal heat transfer

  • Preassembled unit without loose parts

  • Nearly swarfless tapping by tapping equipment of Hütz + Baumgarten

  • Low tapping power

  • Burr - and nearly ledge - free tapping for a maximum of hydraulic power.

  • Leakage free tapping possible by means of a shut off element

  • Extra wide fusion zone

  • Additional barcode for tracing back the fitting (Traceability-Coding)